1. Adjustment to open pressure
Before leaving the plant, the safety valves should adjust their opening pressure to the fixed values required by the user.
Before installation or installation, the user must install a safety valve on site to ensure that the overall pressure value of the safety valve meets the requirements before the valve can be installed on the protected equipment.
The open pressure can be adjusted by changing the spring compression within the working pressure level of the spring, as indicated on the placard.
The pressure of the valve import shall be lowered to % of the open pressure of 90 prior to the spin-regulating bolt, in order to prevent the valve from being rotated as it adjusts the spiral, thereby damaging the seal surface.
In order to ensure the accuracy of the pressure values, adjust the media conditions in the process, such as the type and temperature of the medium, as close as possible to the actual operating conditions.
The opening pressure (for example, from the liquid phase to the gas phase) changes frequently. When the working temperature rises, the opening pressure usually decreases. Therefore, when the temperature of the room is adjusted and used for the high temperature, the fixed pressure value at the room temperature should be slightly higher than the required opening pressure. The height of the valve structure and material selection should be based on the manufacturer’s description.
A conventional safety valve is used to fix additional back pressure. When the open pressure is adjusted after inspection (at this time the back pressure is atmospheric), its fixed value shall be subtracted from the required open pressure value.
2. Adjustment of emission and return pressures
In order to adjust the discharge pressure of the valve and the return pressure, an action test must be performed to bring the valve to full open height. Therefore, it can only be performed after the safety valve has been installed on a large capacity test device or protective equipment.
In the case of the structure of the convection and valves, adjustments are made using a valve-regulating ring. When the coil is broken, a tool such as a fine iron bar is drawn out of the exposed screw, and the gear on the coil can move and rotates around the coil. When the collage is rotated to the left, its position rises, the pressure of discharge and the pressure of return decreases. On the contrary, when the collage is rotated to the right, its position is reduced and the pressure of discharge and return is increased. On each adjustment, adjustments should be made: the circle should not be too wide (generally several gears can be rotated). After each adjustment, adjustments must be made to %, in order to prevent the valves from opening suddenly during the adjustment process, causing accidents.
3 The structure of the upper-down ring (there is a chain of conduct for both the reincarnation and the valve) is complex. Valves are used to change the size of the channel between the valve and the ring, thereby changing the size of the internal pressure build-up between the valve and the ring when the valve is initially opened. When valves rise, the degree of pressure accumulation increases, thereby reducing the proportion of valve openings and thus achieving a sudden and rapid opening. Therefore, increasing valves can reduce the pressure on discharge. It is important to note that valves cannot rise too close to the valve.
The upper circle is used to change the rotation angle of the lower flow medium of the valve, thereby changing the size of the flower's strength, and thus to adjust the echo pressure. When the upper circle rises, the corner is reduced, and the flow is reduced, increasing the echo pressure. On the contrary, when the upper circle is lowered, the echo pressure is reduced.
3. Lead seals
When the safety valve is adjusted, the lead seal is applied to prevent any change in the condition of the adjustment. When the safety valve is repaired, the repositioning of the bolts and the ring should be recorded in front of the disassembly valve to facilitate the adjustment after maintenance.