Proper understanding of the functioning and installation requirements of the stop valve

Source: Shanghai Valve Factory Co., Ltd. | Published: 2023-12-27

The stop valve is a valve that allows the fluid to flow in a fixed direction and automatically prevents its movement in the opposite direction (rewinding). The stop valve is widely used, but this time the focus will be on the stop valve installed on the side of the steam drain valve's export.

Spring-drive stop valve

When the back pressure appears, the valve closes immediately.

In order to ensure reliable operation, the central wizard design prevents large-calibre stop valves from being stuck because of the tilt of the disc.

Must the respirators be installed on the exit side of the steam-drinking valve?

If the condensed water is likely to be rewinding, it will need to be installed. For example, when the condensed water is released to a common catchment, other condensed water reflow equipment from the plume may be generated, and therefore must be installed in such a case. Preventing such rewind is important because it not only affects heating efficiency but may also damage the plume. On the contrary, if the plume is connected to a separate drain, there will be no rewinding, so there is no need to install the rewinding.

Single Private Pipe

If the drain valves are discharged down to the atmosphere through a separate drainage tube, there is generally no reflow hazard and therefore no stop valves are required.

Note: Based on the configuration of the pipe following the water-diplining valve, the back pressure may exceed a pressure and result in a reverse flow if the equipment is in a vacuum or if the pipe rises or falls. In this case, the installation of the stop valve is effective in preventing reversals.

Common water catchments

If the export of the hydrophobic valves is recycled to the same condensed water collection pipe, if no condensing valves are installed, the cooled condensed water released from the operational equipment may flow back to other shut-off equipment.

Note: Based on the configuration of the pipe following the water-diplining valve, the back pressure may exceed a pressure and result in a reverse flow if the equipment is in a vacuum or if the pipe rises or falls. In this case, the installation of the stop valve is effective in preventing reversals.

Common water catchments

If the export of the hydrophobic valves is recycled to the same condensed water collection pipe, if no condensing valves are installed, the cooled condensed water released from the operational equipment may flow back to other shut-off equipment.

Figure C: No stop valves have been installed for the export of the water plume valves.

If a stop valve is installed, even if the export of the water plume is linked to the same catchment pipe, the condensed water released from the operation equipment will not flow back to the other shut-off equipment.

Figure D: Water plume valve exit installation stop valves

You can't get a water hammer if you install a stop valve?

There are many factors for hammers. The most important reason for hammers to be produced in a cooling water recovery pipe is the return flow of condensed water from an lifting tube.

In the recycling pipeline, the reverse flow caused by the lifting tube contributed to the creation of a water hammer.

If the discharge of cold condensed water is carried out through intermittent pumps (e.g. TLVPowerTrapp), if the series is controlled by a switch-controlled power pump, there is a horizontal pipe before the lifting pipe, and the cool condensed water that returns to the lift pipe may collide with the newly ejected condensed water, leading to a hammer. Similarly, when PowerTrapppo is discharged from high-temper condensed water, the collision between the flashing vapour and reflow and the cold condensed water is another possibility created by the water hammer.

In this case, the installation of stop valves (e.g., upgrading of the starting point of the tube) at appropriate locations in the system would be of great help in preventing the occurrence of the hammer.

Figure F: Installation of stop valves at the beginning of the lifting tube

Additional Information

Water hammers resulting from the flow of cryogenic condensation can also help solve problems with stop valves in the cooling water pipeline.

Restrictions on the use of the stop valve

When high-temperature high-pressure condensed water is released to low-pressure areas through water-sorting valves, a certain amount of flash steam is generated. If these flash steam flows into a recovery pipe filled with low-temperature condensed water, the flash steam will pass it to the cool condensed water, so that it can condensate quickly and produce a water hammer. In this case, the installation of a stop valve is ineffective.

Refrigerated condensers cannot be discharged from low-pressure areas to high-pressure pipes. Even when a cut-off valve is installed behind a water-spill valve, it is not possible to release condensed water if the pressure is less than the second pressure at a time.

It is also important to note that if the stop valves are installed after the very low pressure valves, the stop valves themselves will also be a resistance point (i.e., the stop valves will also have pressure impairment), so special attention should be paid to the calculation of the pressure reduction.