Fixed pressure means the predicted pressure of a safe valve valve when it is opened under operating conditions, measured at the surface pressure at the entrance to the valve. Under this pressure, the force of the medium pressure to open the valve under specified operating conditions balances the power of the valve on the valve.

1) Safety valves for steam boilers

a. The pressure shall be determined by the safety valve on the boiler (crash) and the heater, as shown in Table 1.

b. Save the pressure of the safety valves for coals, reheaters and DC boilers to start the separators to equal 1.1 times the working pressure at the installation site.

c. Fixed pressure deviation: ~2.3 MPa time ~2.30 MPa time when the fixed pressure is less than or equal to 0.5 MPa when the total pressure is 0.515 MPa, ~2.3 per cent when the total pressure is 2.3 per cent and ~7.0 MPa time = ±0.07 MPa when the total pressure is > 7.0 MPa time equals 1 per cent of the total pressure.

Form 1 boilers (pot shells) and pressure of safety valves on heaters

Additional work pressure (MPa)

Total pressure of safety valves (MPa)

≤0.8

Work pressure + 0.03

Work pressure +0.05

0.8<P≤5.9

Work pressure is 1.04 times.

1.06 times work pressure

>5.6

1.05 times the work pressure

1.08 times the work pressure

Note: The boiler must have a safety valve, which is regulated by the lower fixed pressure on the table. For a boiler that has a heater, the safety valve should be regulated by lower pressure to ensure that the safety valve on the heater is opened first. The working pressure on the table is the working pressure on the pulse safety valve connecting position, while the other types of safety valves are the working pressure on the installation position of the safety valve.

(2) Use of safety valves for hot water boilers

The total pressure of the safety valve shall be calculated according to Table 2.

b. Fixed pressure deviation: ⁇ 0.015 MPa when fixed pressure is less than or equal to 0.5 MPa, and 3% of the total pressure is fixed when the total pressure is greater than 0.5 MPa.

Table 2

Pressure fixing of hot water boilers with safety valves (MPa)

Work pressure 1.12 times, but not less than work pressure + 0.07 MPa

Work pressure 1.14 times, but not less than work pressure +010 MPa.

Note: The boiler must have a safety valve adjusted to the lower aggregate pressure in the table.

Safety valves are used in stationary pressure containers.

When only one safety valve is installed on a fixed pressure vessel, the fixed pressure of the safety valve shall not be greater than the design pressure of the pressure vessel; when multiple safety valves are installed on the fixed pressure vessel, the fixed pressure of one of the safety valves shall not be greater than the design pressure of the pressure vessel, and the fixed pressure of the other safety valves may be increased appropriately, but shall not exceed the design pressure by 1.05 times.

b. Fixed pressure deviation: ⁇ 0.015 MPa when fixed pressure is less than or equal to 0.5 MPa, and 3% of the total pressure is fixed when the total pressure is greater than 0.5 MPa.

(4) Use of mobile pressure containers with safety valves.

a. The tank design pressure of 1.05 is fixed. ~ The echo pressure is not less than 1.10 times the opening pressure, and the cryogenic cold tank safety valve is not subject to the tank design pressure.

b. Fixed pressure deviation: ⁇ 0.015 MPa when fixed pressure is less than or equal to 0.5 MPa, and 3% of the total pressure is fixed when the total pressure is greater than 0.5 MPa.

Pressure pipe safety valve (5)

a. The maximum working pressure for industrial metal pipelines is set at 1.05 ~1.1 times. The maximum working pressure for pipelines in oil and gas stations is fixed at 1.05 ~ 1.15 times.

b. Fixed pressure deviation: ⁇ 0.015 MPa when fixed pressure is less than or equal to 0.5 MPa, and 3% of the total pressure is fixed when the total pressure is greater than 0.5 MPa.

Use of safety valves for medically high pressure oxygen module (6)

a. Maximum working pressure + 0.02 MPa, total pressure of safety valves.

b. The total pressure deviation is defined as ±0.015 MPa.

(7) Safety valves for compressors

a. Maximum working pressure + 0.02 MPa, total pressure of safety valves.

b. Fixed pressure deviation: ⁇ 0.015 MPa when fixed pressure is less than or equal to 0.5 MPa, and 3% of the total pressure is fixed when the total pressure is greater than 0.5 MPa.